--Version: v6.0.2 --Date: 05/22/2012 --Copyright @ 2012 RLE Technologies. All rights reserved worldwide. --This MIB defines objects for the RLE Wi-MGR/FDS-WI SNMP Agent. RLE-FDSWI-MIB DEFINITIONS ::= BEGIN IMPORTS DisplayString FROM RFC1213-MIB OBJECT-TYPE, enterprises FROM RFC1155-SMI TRAP-TYPE FROM RFC-1215; rle OBJECT IDENTIFIER ::= { enterprises 3184 } products OBJECT IDENTIFIER ::= { rle 1 } fds OBJECT IDENTIFIER ::= { products 10 } fdsWi OBJECT IDENTIFIER ::= { fds 1 } fdsIdent OBJECT IDENTIFIER ::= { fdsWi 1 } fdsIdentManufacturer OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The Monitor Control Unit manufacturer." ::= { fdsIdent 1 } fdsIdentModel OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The Monitor Control Unit Model designation." ::= { fdsIdent 2 } fdsIdentSoftwareVersion OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The SNMP Agent software version." ::= { fdsIdent 3 } fdsSensors OBJECT IDENTIFIER ::= { fdsWi 2 } numberOfSensors OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "The number of sensors recorded by the Wi-MGR/FDS. Used to indicate the number of sensorTable entries." ::= { fdsSensors 1 } sensorTable OBJECT-TYPE SYNTAX SEQUENCE OF InputTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of snmp input object values." ::= { fdsSensors 2 } sensorTableEntry OBJECT-TYPE SYNTAX InputTableEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An input table entry containing data for a specific sensor." INDEX { sensorIndex } ::= { sensorTable 1 } InputTableEntry ::= SEQUENCE { sensorIndex INTEGER, sensorModel DisplayString, sensorID DisplayString, sensorOutOfService INTEGER, sensorSerialNumber DisplayString, sensorRawData1 DisplayString, sensorRawData2 DisplayString, sensorRawData3 DisplayString, sensorConvertedData1 INTEGER, sensorConvertedData2 INTEGER, sensorConvertedData3 INTEGER, sensorAge INTEGER, sensorOfflineDelay INTEGER, sensorLabel DisplayString } sensorIndex OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "The index in the input table for a particular snmp sensor object. Used to address table entries." ::= { sensorTableEntry 1 } sensorModel OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Sensor Model string" ::= { sensorTableEntry 2 } sensorID OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Sensor ID string - two byte ascii string" ::= { sensorTableEntry 3 } sensorOutOfService OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Sensor out of service mode indicator" ::= { sensorTableEntry 4 } sensorSerialNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Sensor Serial Number - sixteen byte ascii string" ::= { sensorTableEntry 5 } sensorRawData1 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Sensor data field #1 in raw hex" ::= { sensorTableEntry 6 } sensorRawData2 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Sensor data field #2 in raw hex" ::= { sensorTableEntry 7 } sensorRawData3 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Sensor data field #3 in raw hex" ::= { sensorTableEntry 8 } sensorConvertedData1 OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "Sensor data field #1 in a converted value based on the sensor model" ::= { sensorTableEntry 9 } sensorConvertedData2 OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "Sensor data field #2 in a converted value based on the sensor model" ::= { sensorTableEntry 10 } sensorConvertedData3 OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "Sensor data field #3 in a converted value based on the sensor model" ::= { sensorTableEntry 11 } sensorAge OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-only STATUS mandatory DESCRIPTION "The age of the sensor data in seconds" ::= { sensorTableEntry 12 } sensorOfflineDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS mandatory DESCRIPTION "The delay time in minutes that a sensor is flagged as out of service" ::= { sensorTableEntry 13 } sensorLabel OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The sensor description label" ::= { sensorTableEntry 14 } fdsWiTrapData OBJECT IDENTIFIER ::= { fdsWi 3 } fdsWiTrapSensorNumber OBJECT-TYPE SYNTAX INTEGER ACCESS not-accessible STATUS mandatory DESCRIPTION "The sensor number (1-400)." ::= { fdsWiTrapData 1 } fdsWiTrapSensorLabel OBJECT-TYPE SYNTAX DisplayString ACCESS not-accessible STATUS mandatory DESCRIPTION "The sensor description label." ::= { fdsWiTrapData 2 } fdsWiTrapSensorText OBJECT-TYPE SYNTAX DisplayString ACCESS not-accessible STATUS mandatory DESCRIPTION "A text string associated with the sensor trap." ::= { fdsWiTrapData 3 } fdsWiTraps OBJECT IDENTIFIER ::= { fdsWi 4 } fdsWiSensorAlarmTrap TRAP-TYPE ENTERPRISE fdsWiTraps VARIABLES { fdsWiTrapSensorNumber, fdsWiTrapSensorLabel, fdsWiTrapSensorText } DESCRIPTION "A sensor has reached an alarm state." ::= 1 fdsWiSensorWarningTrap TRAP-TYPE ENTERPRISE fdsWiTraps VARIABLES { fdsWiTrapSensorNumber, fdsWiTrapSensorLabel, fdsWiTrapSensorText } DESCRIPTION "A sensor has reached a warning state." ::= 2 fdsWiSensorOfflineTrap TRAP-TYPE ENTERPRISE fdsWiTraps VARIABLES { fdsWiTrapSensorNumber, fdsWiTrapSensorLabel, fdsWiTrapSensorText } DESCRIPTION "A sensor has went offline." ::= 3 fdsWiSensorReturnToNormalTrap TRAP-TYPE ENTERPRISE fdsWiTraps VARIABLES { fdsWiTrapSensorNumber, fdsWiTrapSensorLabel, fdsWiTrapSensorText } DESCRIPTION "A sensor alarm/warning has returned to normal." ::= 4 fdsWiOptions OBJECT IDENTIFIER ::= { fdsWi 5 } fdsWiOptionCard OBJECT-TYPE SYNTAX INTEGER { DigitalIoEnabled(0), DigitalIoDisabled(1), DigitalIoNotInstalled(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Fds-Wi option card installation setting" ::= { fdsWiOptions 1 } fdsWiDigitalInputs OBJECT IDENTIFIER ::= { fdsWiOptions 2 } fdsWiDigitalInput1 OBJECT IDENTIFIER ::= { fdsWiDigitalInputs 1 } fdsWiDigitalInput1Reading OBJECT-TYPE SYNTAX INTEGER { Inactive(0), Active(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "The reading for digital input 1. The reading will be 1 (active) or 0 (inactive)" ::= { fdsWiDigitalInput1 1 } fdsWiDigitalInput1Text OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "A user-defined text string associated with Digital Input Number 1." ::= { fdsWiDigitalInput1 2 } fdsWiDigitalInput2 OBJECT IDENTIFIER ::= { fdsWiDigitalInputs 2 } fdsWiDigitalInput2Reading OBJECT-TYPE SYNTAX INTEGER { Inactive(0), Active(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "The reading for digital input 2. The reading will be 1 (active) or 0 (inactive)" ::= { fdsWiDigitalInput2 1 } fdsWiDigitalInput2Text OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "A user-defined text string associated with Digital Input Number 2." ::= { fdsWiDigitalInput2 2 } fdsWiDigitalInput3 OBJECT IDENTIFIER ::= { fdsWiDigitalInputs 3 } fdsWiDigitalInput3Reading OBJECT-TYPE SYNTAX INTEGER { Inactive(0), Active(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "The reading for digital input 3. The reading will be 1 (active) or 0 (inactive)" ::= { fdsWiDigitalInput3 1 } fdsWiDigitalInput3Text OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "A user-defined text string associated with Digital Input Number 3." ::= { fdsWiDigitalInput3 2 } fdsWiDigitalInput4 OBJECT IDENTIFIER ::= { fdsWiDigitalInputs 4 } fdsWiDigitalInput4Reading OBJECT-TYPE SYNTAX INTEGER { Inactive(0), Active(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "The reading for digital input 4. The reading will be 1 (active) or 0 (inactive)" ::= { fdsWiDigitalInput4 1 } fdsWiDigitalInput4Text OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "A user-defined text string associated with Digital Input Number 4." ::= { fdsWiDigitalInput4 2 } fdsWiDigitalInput1Trap TRAP-TYPE ENTERPRISE fdsWiTraps VARIABLES { fdsWiDigitalInput1Text } DESCRIPTION "Digital Input Number 1 has reached a warning state." ::= 11 fdsWiDigitalInput2Trap TRAP-TYPE ENTERPRISE fdsWiTraps VARIABLES { fdsWiDigitalInput2Text } DESCRIPTION "Digital Input Number 2 has reached a warning state." ::= 12 fdsWiDigitalInput3Trap TRAP-TYPE ENTERPRISE fdsWiTraps VARIABLES { fdsWiDigitalInput3Text } DESCRIPTION "Digital Input Number 3 has reached a warning state." ::= 13 fdsWiDigitalInput4Trap TRAP-TYPE ENTERPRISE fdsWiTraps VARIABLES { fdsWiDigitalInput4Text } DESCRIPTION "Digital Input Number 4 has reached a warning state." ::= 14 END